    • #18046
      mattthomas2015
      Participant

      I have this generator with 24hrs on it. I’m not sure what happened to it but it does not display any hertz or voltage on any of the lines while running. Seeking any help, appreciate the help!

    • #18048
      trekkerlife1
      Participant

      There are several things that can cause this, so more info is needed. Here are a few things to check first.
      * any alarm lights on?
      * all engine gauges (oil, temp, rpm) nominal? No surging?
      * check regulator fuses? (Behind panel)
      * check 24v fuse and 50/60 hz setting?

      If none of the above, then I would suspect a voltage regulator problem…. There are several posts on how to diagnose this…

      Good luck!

    • #18049
      GMG
      Keymaster

      Sorry, but this is too general of a comment. Need to check master breaker, make sure that the read-out setting corresponds to the desired voltage/phase output you have set. Please download free manuals from out website.