Hi all I am new here. I have an issue with a MEP003A, it will not produce 220 volts. I have my settings correct, I changed the voltage adjustment switch on the panel, it did not change.
Any insights would be greatly appreciated. Thank you
Hmmm… 130v is suspicious…. Is it really 130v? Check real voltage at AC outlet on front panel…
Should be a clean 120v on each L1, L2, L3 settting…
Are ALL selector settings the same voltage? That should never happen!
Only the L1-L2, L2-L3, L1-L3 settings should be 240v….
Check your earth ground? It Should be connected to a rod 6’-8’ in the ground, or tied to rebar in a concrete slab… and N&G should be connected together at the terminal block…
Also, no alarm Lights are on??
No alarm lights
Any guess ?
Update went to take voltage readings tonight and discovered the AC output reconnection switch was not fully engaged in the 120/240V position
Fully engaged the switch and everything is perfect
Thank you for all of your input